SQ0214 SYNCHROSCOPE.
SQ0214 SYNCHROSCOPE
Synchronization Meter.
The SQ0214 is a microprocessor-based synchronization meter (synchro scope).
It is designed for manual or semi-automatic synchronization of a generator with a bus bar by measuring phase difference, voltage, and frequency.
manufactured by Iskra.
Key Technical Specifications
-
- Measurement Capabilities: It functions as five instruments in one, replacing two voltmeters, two frequency meters, and a phase difference meter.
- Display:
-
- LED Circle: 24 LEDs display momentary phase difference (Δϕcap delta phi Δ𝜙) with 20° resolution, increasing to 5° within the synchronizing range
- (±15°plus or minus 15 degrees±15°).
- LCD: A backlit LCD displays generator
- (UGEN cap U sub cap G cap E cap N end-sub 𝑈𝐺𝐸𝑁) and bus-bar
- (UBB cap U sub cap B cap B end-sub𝑈𝐵𝐵) voltages, along with both frequencies
- (fGENf sub cap G cap E cap N end-sub𝑓𝐺𝐸𝑁and
- fBBf sub cap B cap B end-sub𝑓𝐵𝐵) orΔϕcap delta phiΔ𝜙.
-
- Synchronizing Settings: Rear potentiometers allow for adjusting:
-
- Phase difference (Δϕcap delta phi Δ𝜙):
- typically 2…20°el2 … 20 °el2…20°el.
- Voltage difference (ΔUcap delta cap UΔ𝑈):
- typically 1…10%1 … 10 %1…10%.
- Delay time (DELAY): typically 0.1…1 s0. 1 … 1 s 0.1…1 s.
-
- Operating Range: Standard frequency range is 40–70 Hz or 45–65 Hz depending on the model.
- Safety & Compliance: Rated for Installation Category III, Pollution Degree 2, and typically carries CE and ship-specific certifications like
- Bureau Veritas. Core Functionality
- Synchronization Relay: Activates (pulse or continuous) when pre-set phase, voltage, and delay conditions are met.
- “Dead Bus Bar” Function: Can be configured to allow synchronization when the generator is live but the bus bar is dead (below a certain noise level, e.g., 10–40%).
- Status Output: An open-collector output monitors microprocessor health, changing from low to high impedance if a malfunction occurs.
- Housing: Standard DIN housing, either 96 x 96 mm or 144 x 144 mm.